Article ID Journal Published Year Pages File Type
4918767 Energy and Buildings 2017 13 Pages PDF
Abstract
Application of the proposed method is demonstrated using two cases studies: (1) a TRNSYS model of a water-cooled chiller in a mixed-use building in Singapore, and (2) an EnergyPlus model of the cooling system of an office building in Pennsylvania, U.S.A. In both case studies, convergence was achieved for all parameters of the posterior distribution, with Gelman-Rubin statistics Rˆ within 1 ± 0.1. The coefficient of variation of the root mean squared error (CVRMSE) and normalized mean biased error (NMBE) were also within the thresholds set by ASHRAE Guideline 14 [1].
Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, , , ,