Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
492970 | Simulation Modelling Practice and Theory | 2010 | 14 Pages |
Abstract
Non-flammable characteristic of cast-resin dry-type transformers make them suitable for different kind of usages. This paper presents a method of how to obtain high frequency model of these transformers. For this purpose a detailed model is used and parameters of the model including inductances, capacitances and resistances are calculated using FEM (finite elements method). The effect of the frequency is considered in the inductance calculation using FEM. In order to validate the model, a setup was constructed for testing on high-voltage winding of dry-type transformer. The simulation results were compared with the experimental data measured from FRA (frequency response analysis) and impulse tests.
Related Topics
Physical Sciences and Engineering
Computer Science
Computer Science (General)
Authors
M. Eslamian, B. Vahidi, S.H. Hosseinian,