Abstract
The priority to reactive power contribution from the Voltage Source Converter (VSC) based High Voltage Direct Current (HVDC) connection to support the grid during faults as suggested by the modern Network Code (NC) for HVDC affects the distance protection of transmission lines. Moreover, suppressing the negative sequence current during an unbalanced condition also interferes with the proper operation of the distance relays. This is because the current contribution from the converter is limited in magnitude and modified in the waveform in order to protect the power electronic devices during the fault in comparison to the synchronous generator fault current characteristics. This paper discusses the cause as well as the severity of the problems faced by the distance protection of transmission lines connected to the VSC based HVDC system by analyzing the apparent impedance analytically and in the simulation. The response of the relay to balanced and unbalanced faults lying on transmission lines is investigated. It is shown that the VSC limited reactive support and suppressed negative sequence current affect fault detection, forcing the relay to malfunction. The results of this paper can be used as a reference for understanding the effects of VSC-HVDC system on the operation of the distance protection during faults.