Article ID Journal Published Year Pages File Type
4945580 International Journal of Electrical Power & Energy Systems 2018 8 Pages PDF
Abstract

•A novel intelligent algorithm for fault location on VSC-HVDC system is proposed.•This method with makes full use of frequency, time and energy. And it capture the fault features via Hilbert-Huang Transform.•The bat algorithm optimizes the parameters of the model. High-frequency variance contribution rate is adopted to identify the fault area.•The expected accuracy of the proposed method is ±500 m.•The model is also applicable for hybrid transmission systems.

This paper proposes a novel intelligent algorithm for fault location on the voltage sourced converter-high voltage direct current (VSC-HVDC) system. This method with single-ended measurement makes full use of frequency, time and energy to capture the fault features via Hilbert-Huang Transform (HHT). The time delay, characteristic frequency, energy attenuation and high-frequency energy are used as the input of ε-support vector regression (SVR) to get fault distance. Then bat algorithm (BA) optimizes the parameters of the model with cross validation comparing with other optimization algorithm. Furthermore, high-frequency variance contribution rate (HVCR) is adopted to identify the fault area. The VSC-HVDC simulation system is constructed to verify the reliability and accuracy of the method and the expected accuracy of the proposed method is ±500 m. The results demonstrated that the proposed method still has reliability and accuracy for hybrid transmission line with a small amount of data.

Related Topics
Physical Sciences and Engineering Computer Science Artificial Intelligence
Authors
, , , ,