Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
4990941 | Applied Thermal Engineering | 2017 | 14 Pages |
Abstract
An experimental investigation was made to study the performance of a double pipe heat exchanger, with a triangular copper fins, which is used to extend the outside surface area of the tube. While, an external type of enhancement is used for the inside of the tube by using twisted tapes with various twisted ratio inserts inside the tube. Results for ninety experiments were indicated. These runs were done for plain tube, finned tube and finned tube with twisted tape at three different twisting ratios. Experiments were performed at various Reynolds number for the above profiles both in the inner and outer tube. The results showed that the overall heat transfer coefficient rate for only a finned pipe is (3 times) greater than plane pipe. Furthermore, as the twisted tape ratio used in the inner pipe at (7, 5, 3), the heat transfer rate was increases 4, 6, 8 times the case of plain pipe, respectively. Conversely, the pressure drop and friction factor increase across the inner tube with the decreasing of the twisted tape ratio increasing. The measured and calculated results show the most effective heat exchanger among cases studied in this which is the finned tube with twisted tape at ratio 3.
Related Topics
Physical Sciences and Engineering
Chemical Engineering
Fluid Flow and Transfer Processes
Authors
Vinous M. Hameed, Maha A. Hussein,