Article ID Journal Published Year Pages File Type
644826 Applied Thermal Engineering 2016 12 Pages PDF
Abstract
Due to tight thermal integration and the requirement for large volumetric flow rates, air ducting of a power plant is boxy in structure and contains abrupt changes in flow direction and cross-section, flow splits and mergers. Achieving a desired flow distribution among several possible paths is therefore a difficult task. In recent years, computational fluid dynamics (CFD) has emerged as a useful tool for flow analysis in a number of industrial applications. In the present study, a flow control algorithm is developed for optimally locating guide vanes in header manifolds to achieve a desired flow distribution. It is based on evaluating approximately the sensitivity of flow distribution at a flow split to the orientation of guide vanes. A simple gradient-based method has been developed which enables a robust, automated procedure for finding the optimal orientation of guide vanes in a small number of CFD computations. Its application to a typical industrial flow situation containing sharp bends and flow splits has been illustrated through a case study and verified experimentally.
Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes
Authors
, ,