Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
645160 | Applied Thermal Engineering | 2016 | 7 Pages |
Abstract
The energy consumption of data centers is increasing rapidly with the development of technology. In order to reduce the energy consumption, free cooling technology instead of the conventional refrigeration system is feasible in the cold season. In the present work, a pump-driven two phase cooling system which is an excellent free cooling technology was developed and the prototype was investigated experimentally. The experimental results show that the efficiency of the magnetic pump was 7.7% at the motor frequency of 22âHz, the cooling capacity of the system was able to reach 3.429âkW and 9.241âkW when the temperature differences between indoor and outdoor were 10â°C and 25â°C, respectively, and the EER were 12.9 and 29.7, which are extremely higher than the conventional refrigeration system.
Keywords
Related Topics
Physical Sciences and Engineering
Chemical Engineering
Fluid Flow and Transfer Processes
Authors
Yuezheng Ma, Guoyuan Ma, Shuang Zhang, Feng Zhou,