Abstract
The sorption capacity of the composite material increased dramatically after being impregnated with LiCl. Among the four tested samples, WSS + 40 wt% LiCl exhibits the best performance. A regeneration temperature of 80 °C appears to be optimal for obtaining both a high COP and high specific cooling power. A lower condensation temperature can increase the cooling power. The sorption and desorption times of 60 min yield a reasonable compromise between cooling COP and mass specific cooling powers. The developed sorption air cooler system using WSS + 40 wt% LiCl can store heat at temperatures below 100 °C and produce cooling energy with a cooling coefficient of performance (COP) of approximately 0.3.
Keywords
Related Topics
Physical Sciences and Engineering
Chemical Engineering
Fluid Flow and Transfer Processes
Authors
Hongzhi Liu, Katsunori Nagano, Atsushi Morita, Junya Togawa, Makoto Nakamura,