Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
645650 | Applied Thermal Engineering | 2015 | 7 Pages |
Abstract
The optimized refrigerant circuitry design was implemented in a new prototype evaporator, which replaced the original evaporator in the tested RTU system. Laboratory tests of the new system showed an improvement of 2.2 ± 1.5% in capacity and 2.9 ± 1.5% in COP compared to the performance of the original system, which was optimized by the manufacturer using conventional methods prior to the onset of this study.
Keywords
Related Topics
Physical Sciences and Engineering
Chemical Engineering
Fluid Flow and Transfer Processes
Authors
D.A. Yashar, S. Lee, P.A. Domanski,