Abstract

In order to check the theoretical performance of the new working fluid LiBr + LiNO3+H2O (mole ratio of LiBr and LiNO3 = 4:1), the theoretical coefficients of performance (COP) of this working fluid and LiBr + H2O were calculated at various operating conditions. The improvement of crystallization problem was also checked. This proposed working fluid was proved to increase the COP by about 5% than LiBr + H2O. The cooling water through absorber and evaporator was heated to higher temperature by this new working fluid. LiBr + LiNO3 + H2O was found to be an alternative to the conventional LiBr + H2O with higher COP and less corrosivity.

Research highlights► New working pair. ► Complete model of absorption heat pumps. ► Performance improvement. ► Good feasibility in practice.

Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes