Article ID Journal Published Year Pages File Type
648493 Applied Thermal Engineering 2008 9 Pages PDF
Abstract

Two-phase frictional pressure gradient is significantly affected by the flow patterns. Though most of the U-type wavy tubes are commonly vertically installed in the air-conditioning and refrigerating systems, yet none investigations had reported the two-phase frictional pressure loss in vertical U-type wavy tubes. This study presents the measurements of R-134a two-phase frictional pressure gradient subject to vertical and horizontal arrangements of a U-type wavy tube with inner diameter of 5.07 mm and a curvature ratio of 5. The ratio between two-phase pressure gradients of U-bend and straight tube is about 2.5–3.5. For the straight tube, the frictional two-phase pressure gradient ratio between the vertical and horizontal arrangements is marginally higher (1.0–1.2) for annular flow pattern at x > 0.5, and is 1.0–1.4 for the U-bend in the wavy tube. The higher resistance in the vertical arrangement is due to the buoyancy force against the flow inertia. However, for x < 0.5, this ratio is gradually increased due to the difference of flow pattern. The ratio is increased to 1.8 in the straight tube. For the U-bend, the ratio is 2.1 for flow entering the upper tube and is 1.5 for flow entering the lower tube at x = 0.1 and G = 200 kg/m2 s. For the vertical wavy tube, additional effects like the flow pattern transition, liquid flow reversal, and freezing slug may cause additional pressure drops.

Keywords
Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes
Authors
, , , ,