Article ID Journal Published Year Pages File Type
648791 Applied Thermal Engineering 2009 7 Pages PDF
Abstract
An experimental study was performed on compact finned tube heat exchangers under wet conditions. Eight different finned tube heat exchangers having slit fins with hydrophilic coatings were tested. The effects of tube diameter, the number of tube rows, and inlet air relative humidity on air side heat transfer and pressure drop characteristics were investigated. Air side heat transfer coefficients were calculated using the log mean enthalpy difference method. The effects of the number of tube rows and the tube diameter on the Colburn j-factor and the f-factor were larger compared with those of the inlet air relative humidity. The Colburn j-factor and the f-factor of the single-row heat exchanger were larger than those of two- or three-row heat exchangers. The j-factor for the 5.30 mm tube diameter was compared with those for 7.35 mm and 9.95 mm tube diameters at 46% RH and was found to be 33% and 55% larger, respectively.
Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes