Article ID Journal Published Year Pages File Type
649381 Applied Thermal Engineering 2007 8 Pages PDF
Abstract

This paper presents an experimental investigation of the thermal performances of a forced draft counter flow wet cooling tower filled with an “VGA” (Vertical Grid Apparatus) type packing. The packing is 0.42 m high and consists of four (04) galvanised sheets having a zigzag form, between which are disposed three (03) metallic vertical grids in parallel with a cross sectional test area of 0.0222 m2 (0.15 m × 0.148 m). This study investigates the effect of the air and water flow rates on the cooling water range as well as the tower characteristic, for different inlet water temperatures. Two operating regimes were observed during the air water contact, a pellicular regime (PR) and a bubble and dispersion regime (BDR). These two regimes can determine the best way to promote the heat transfer. The BDR regime seems to be more efficient than the pellicular regime, as it enables to cool larger water flow rates. The comparison between the obtained results and those found in the literature for other types of packing indicates that this type possesses very interesting thermal performances.

Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes
Authors
, , ,