A mass flow correlation for R134a through an EEV (electronic expansion valve) is developed from extensive experimental data. The refrigerant mass flow characteristics of the EEV are an important issue in heat pump/refrigeration system operation because the valve regulates the refrigerant flow to match various operating conditions. Based on the throttling mechanism and thermodynamic analysis, the mass flow rate is a function of various parameters. The selected decision parameters include the valveā€™s geometric parameters, the inlet refrigerant pressure and temperature, the outlet refrigerant pressure, and the refrigerant thermophysical properties represented by the dynamic viscosity and the surface tension, which are sufficient and irredundant for determining the flow coefficient. Because these parameters have very complex and coupled effects on the mass flow characteristics, two combined non-dimensional parameters are defined to describe the coupled effects based on the influence and uncertainty analysis of parameters. The experimental results illustrate that the defined non-dimensional parameters can reveal the EEV flow characteristics correctly. Then, the semi-theoretical flow coefficient correlation with respect to the defined non-dimensional parameters is proposed and identified from several hundred sets of experimental samples using multivariable regression analysis. The proposed correlation agrees well with experimental data for R134a within a wide range of operating conditions. The investigation method in this paper can be adopted by the flow characteristics studies for other types of the EEVs and refrigerants.

Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes
Authors
, , ,