Abstract

This paper reports an experimental investigation of heat-transfer and pressure-drop behavior of R-290, R-600, and R-290/R-600 in the three-lines serpentine small-diameter (2.46 mm) tube bank. Heat transfer coefficients and pressure drop characteristics are measured for a range of heat flux (5–21 kW/m2), mass flux (250–500 kg/m2 s), equilibrium mass quality (0–0.86), and the fixed mixture composition ((R-290/R-600 (55 wt.%/45 wt.%)). The results show that the flow boiling heat transfer coefficients for R-290, R-600, and R-290/R-600 are 1.66–1.96-fold, 1.28–1.38-fold and 1.57–1.88-fold greater as compared with those for R-134a under equal heat and mass fluxes. Also, the two-phase flow frictional pressure drop for R-600, R-290/R-600 and R-290 are 1.41–1.60-fold, 1.32–1.50-fold and 1.22–1.40-fold smaller as compared with that for R-134a. A new heat transfer correlation was presented by using a superposition model to predict the experimental data for both pure refrigerants and refrigerant mixtures. Experimental results were compared with several correlations which predict the evaporative heat transfer, which are in good agreement with experimental data.