Abstract
To achieve these targets, two CO2 finned-tube gas coolers/condensers with different structural designs and controls have been purposely built, instrumented and connected with an existing test rig of a CO2 booster refrigeration system. Consequently, the performance of the CO2 gas coolers/condensers with different structure designs, controls and system integration at different operating conditions can be thoroughly investigated through experimentation. In the meantime, models of the finned-tube CO2 gas coolers/condensers have been developed using both the distributed (detailed model) and lumped (simple model) methods. The former is employed to give a detailed prediction of the working fluid temperature profiles, localised heat transfer rates and effects of pipe circuitry arrangements, while the latter is suitable for the simulation and optimisation of system integration with less computation time. Both models have been validated with measurements, and moreover the simple model has been integrated with other component models so as to create a system model. The effects of the CO2 gas cooler/condenser sizes and controls on the system performance can thus be compared and analysed.