When the surface temperature of the outdoor coil in an air source heat pump (ASHP) unit is lower than both freezing point of water and the air dew point, frost can be formed and accumulated over outdoor coil surface. Frosting affects the energy efficiency, and periodic defrosting therefore is necessary. Reverse cycle defrosting is currently the most widely used defrosting method. A previous related study has indicated that during reverse cycle defrosting, downwards flow of the melted frost over a multi-circuit outdoor coil could affect the defrosting performance, without however giving detailed quantitative analysis of the effects. Therefore an experimental study on the effects has been carried out and a quantitative analysis conducted using the experimental data. In this paper, the detailed description of an experimental ASHP unit which was specifically built up is firstly reported. This is followed by presenting experimental results. Result analysis and conclusions are finally given.