Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
6859978 | International Journal of Electrical Power & Energy Systems | 2015 | 12 Pages |
Abstract
In this research, a 20Â kV switchgear panel has been subjected to PD faults in the laboratory and measurements have been carried out by using different non-intrusive sensors including a novel sensor, the D-dot sensor and recorded by a high frequency oscilloscope. The measured results show the effective applicability of sensors for switchgear. The Discrete Wavelet Transform (DWT) has been used to de-noise PD signals in this paper. Time domain and frequency domain comparison of original and de-noised PD signals reveals the significance of this technique for online monitoring of Medium Voltage (MV) switchgear. Finally, an adaptive online de-noising concept, based on automatic de-noising is also proposed in this paper.
Related Topics
Physical Sciences and Engineering
Computer Science
Artificial Intelligence
Authors
Ghulam Amjad Hussain, Muhammad Shafiq, Lauri Kumpulainen, Farhan Mahmood, Matti Lehtonen,