Abstract
Due to incorporation of series capacitor compensation in transmission line for stability improvement, subsynchronous oscillations are generated at turbine-generator shaft. These oscillations can damage the shaft system if these are not well suppressed. In order to damp out these oscillations, usually power system network should have sufficient damping and the increase of network damping is obtained by the injection of subsynchronous component of voltage and current into the line, which are extracted from the measured signal of the system. However, the effectiveness of damp out of these subsynchronous oscillations is possibly by incorporating UPFC in the transmission line network is of high interest and it should be further investigated. This research article proposes the mitigation of subsynchronous resonance (SSR) using fractional-order PI (FOPI) based unified power flow controller (UPFC). The robustness of the proposed controller is tested for 25%, 55% and 70% series compensation with a symmetrical fault (L-L-L fault). Further, Eigenvalue analysis and Fast Fourier Transform (FFT) analysis against operating point variations and uncertainties in the system are also examined. The IEEE first benchmark model is adopted for this study and the superiority of the FOPI based UPFC controller over PI based UPFC controller is discussed by comparing the results with various performance indices.
Related Topics
Physical Sciences and Engineering Computer Science Signal Processing
Authors
, , , ,