Article ID Journal Published Year Pages File Type
700085 Control Engineering Practice 2009 13 Pages PDF
Abstract

This work deals with a procedure for model re-identification of a process in closed loop with an already existing commercial MPC. The controller considered here has a two-layer structure where the upper layer performs a target calculation based on a simplified steady-state optimization of the process. Here, it is proposed a methodology where a test signal is introduced in a tuning parameter of the target calculation layer. When the outputs are controlled by zones instead of at fixed set points, the approach allows the continuous operation of the process without an excessive disruption of the operating objectives as process constraints and product specifications remain satisfied during the identification test. The application of the method is illustrated through the simulation of two processes of the oil refining industry.

Related Topics
Physical Sciences and Engineering Engineering Aerospace Engineering
Authors
, , ,