Liquid desiccant technology in central air conditioning system is very promising, however, rare researchers proposed to carry out it on household liquid desiccant air conditioner. In this paper, a two-dimensional heat and mass transfer theoretical model of cross flow dehumidifier for household split air conditioner has been established, and it is shown that the model established has a good accuracy and the relative error is less than 3.72% by comparing the simulation results with the experimental data in the literature. Based on the model, a series of experiments are conducted and the experiment data is adopted to fit the correlation formula of NTUm and Le. The results show that the model established has a good reaction to the actual situation. Furthermore, the influence of air, solution inlet conditions on the dehumidification performance of the system has been discussed in the paper.