Abstract
Combined Cooling, Heating, and Power (CCHP) systems with cool thermal storage can provide an appropriate energy supply for data centers. In this work, we evaluate the CCHP system performance under two different operation strategies, i.e., following thermal load (FTL) and following electric load (FEL). The evaluation is performed through a case study by using TRNSYS software. In the FEL system, the amount of cool thermal energy generated by the absorption chillers is larger than the cooling load and it can be therefore stored and reused at the off-peak times. Results indicate that systems under both operation strategies have advantages in the fields of energy saving and environmental protection. The largest percentage of reduction of primary energy consumption, CO2 emissions, and operation cost for the FEL system, are 18.5%, 37.4% and 46.5%, respectively. Besides, the system performance is closely dependent on the equipment selection. The relation between the amount of energy recovered through cool thermal storage and the primary energy consumption has also been taken into account. Moreover, the introduction of cool thermal storage can adjust the heat to power ratio on the energy supply side close to that on the consumer side and consequently promote system flexibility and energy efficiency.
Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes