Article ID Journal Published Year Pages File Type
7047582 Applied Thermal Engineering 2016 11 Pages PDF
Abstract
In single screw refrigeration compressor (SSRC), the Multicolumn Envelope Meshing Pair (MEMP) was proposed to reduce the wear of the meshing pair. However, the application of this new type meshing pair will change the thermodynamic performance of SSRC. It is necessary to research the thermodynamic performance of the SSRC with MEMP to evaluate the value of the proposed MEMP. In this paper, a theoretical calculation model describing the working process of the SSRC with MEMP is established to predict the thermodynamic performance of the SSRC. Experimental investigations on the performance of a SSRC with MEMP under different conditions are also carried out to verify the theoretical calculation model. Obtained results show that the theoretical calculation results are in good agreement with the experimental ones, which means that the presented theoretical calculation model is a powerful tool for performance analysis of the SSRC with MEMP. With the validated model, thermodynamic performances of the SSRC with MEMP have been analyzed. The SSRC with MEMP is proved to have high volume displacement and volumetric efficiency but needs slightly more shaft power. The maximum increment of shaft power and volumetric efficiency of SSRC with MEMP is 5.06% and 3.7% respectively in all working conditions.
Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes
Authors
, , , , ,