Article ID Journal Published Year Pages File Type
788640 International Journal of Refrigeration 2015 18 Pages PDF
Abstract

•Exergoeconomic analyses of the new desiccant-evaporative air-conditioning system.•Exergoeconomic analyses on different regeneration and references temperatures.•Exergoeconomic analyses performances for the system and components.

This paper presented the exergoeconomic evaluation of the developed desiccant-evaporative air-conditioning system. The developed system was evaluated based on the steady-state conditions at different regeneration and reference temperatures. The exergoeconomic evaluation method was implemented to the system components and the whole system to evaluate the exergy efficiency, exergy destruction ratios, cost rates, relative cost differences and exergoeconomic factors. The regeneration and reference temperatures affected the exergy efficiencies, exergy destruction ratios, cost rates, relative cost differences and exergoeconomic factors. The desiccant wheel, heating coil and evaporative cooler had a high cost rate (investment cost, operation and maintenance cost, and exergy destruction cost). The exit air fan, outdoor air fan and evaporative cooler had a high relative cost difference. The exit air fan, outdoor air fan and secondary heat exchanger had a high exergoeconomic factor. Replacement of the desiccant wheel with a higher dehumidification performance could decrease the high cost rate. A higher efficiency evaporative cooler and heating coil were needed. Cheaper air fans (outdoor air fans and exit air fans) were needed.

Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , , , ,