Article ID Journal Published Year Pages File Type
789720 International Journal of Refrigeration 2010 10 Pages PDF
Abstract

This paper is concerned with the experimental analysis of a standard terminal fan-coil unit with ice slurry as coolant. The ice slurry was produced from an ethylene glycol 10 wt% aqueous solution. The pressure drop measurements are presented as a function of volumetric flow rate, ice concentration and Reynolds number. The experimental friction factors are obtained and discussed. The fan-coil capacity was experimentally determined for chilled water and melting ice slurry with inlet ice fractions around 5, 10, 15 and 20 wt%, considering in each case three different fan rotation velocities. The fan-coil capacity is higher with melting ice slurry than with chilled water by factors between 3.7 and 4.9. The heat transfer analysis realizes that the air side thermal resistance controls the heat transfer process. Experimental results for the melt off rate of ice in the fan coil and the superheating at the fan-coil outlet are shown and discussed.

Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , , ,