Abstract
This paper proposes a special protection scheme to prevent power system blackout due to a sequence of relay trip events based on phasor measurement units (PMUs). In a control center, we use PMU's to monitor the generators and the major EHV transmission lines of a power system, and apply an instability prediction algorithm for initiating a special protection schemes (SPS) to avoid a sequence of relay trip events whenever necessary. When a fault happens, we group the generators swinging coherently and reduce the system to One-Machine-Infinite-Bus (OMIB) system. The remedial control actions consist of load shedding and generation tripping. The strategy for determining the amount of remedial control actions is a proposed relay setting limited equal-area criterion for OMIB. A case study of Taiwan power system assumed to be equipped with proposed special protection scheme is conducted. Encouraging results are obtained.
Related Topics
Physical Sciences and Engineering Computer Science Artificial Intelligence
Authors
, , ,