Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
6859661 | International Journal of Electrical Power & Energy Systems | 2015 | 8 Pages |
Abstract
The paper presents a Mixed Integer Linear Programming (MILP) model for the solution of the three-phase volt/var optimization (VVO) of medium voltage unbalanced distribution feeders. The VVO of a distribution feeder is aimed at calculating the most efficient operating conditions by means of the scheduling of transformers equipped with an on-load tap changer and distributed reactive power resources (such as embedded generators and switchable capacitors banks). The proposed model allows the representation of feeders composed by three-phase, two-phase, and single-phase lines, by transformers with different winding connections, by unbalanced wye- and delta-connected loads, by three-phase and single phase capacitor banks and embedded generators. The accuracy of the results is verified by using IEEE test feeders.
Keywords
Related Topics
Physical Sciences and Engineering
Computer Science
Artificial Intelligence
Authors
Alberto Borghetti, Fabio Napolitano, Carlo Alberto Nucci,