کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
2640572 1563566 2007 5 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Thermal disinfection of hotels, hospitals, and athletic venues hot water distribution systems contaminated by Legionella species
موضوعات مرتبط
علوم زیستی و بیوفناوری ایمنی شناسی و میکروب شناسی میکروب شناسی
پیش نمایش صفحه اول مقاله
Thermal disinfection of hotels, hospitals, and athletic venues hot water distribution systems contaminated by Legionella species
چکیده انگلیسی

Legionella spp. (≥500 cfu liter−1) were detected in 92 of 497 water distribution systems (WDS) examined. Thermal disinfection was applied at 33 WDS. After the first and second application of the disinfection procedure, 15 (45.4%) and 3 (9%) positive for remedial actions WDS were found, respectively. Legionella pneumophila was more resistant to thermal disinfection than Legionella non-pneumophila spp. (relative risk [RR] = 5.4, 95% confidence intervals [CI] = 1–35). WDS of hotels with oil heater were more easily disinfected than those with electrical or solar heater (RR = 0.4 95% CI = 0.2–0.8). Thermal disinfection seems not to be efficient enough to eliminate legionellae, unless repeatedly applied and in combination with extended heat flushing, and faucets chlorine disinfection.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: American Journal of Infection Control - Volume 35, Issue 9, November 2007, Pages 623–627