کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
249234 | 502602 | 2010 | 7 صفحه PDF | دانلود رایگان |
In the warm and humid climate zone, air-conditioning (AC) is usually provided at working places to enhance human thermal comfort and work productivity. From the building sustainability point of view, to achieve acceptable thermal sensation with the minimum use of energy can be desirable. A new AC design tactic is then to increase the air movement so that the summer temperature setting can be raised. A laboratory-based thermal comfort survey was conducted in Hong Kong with around 300 educated Chinese subjects. Their thermal sensation votes were gathered for a range of controlled thermal environment. The result analysis shows that, like in many other Asian cities, the thermal sensation of the Hong Kong people is sensitive to air temperature and speed, but not much to humidity. With bodily air speed at 0.1–0.2 m/s, clothing level 0.55 clo and metabolic rate 1 met, the neutral temperature was found around 25.4 °C for sedentary working environment. Then recommendations are given to the appropriate controlled AC environment in Hong Kong with higher airflow speeds.
Journal: Building and Environment - Volume 45, Issue 10, October 2010, Pages 2177–2183