کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
263762 | 504083 | 2012 | 8 صفحه PDF | دانلود رایگان |
This paper presents the results of experimental research on 8 plate heat exchangers. Their purpose is to heat water for radiator heating system and domestic hot water. Measurements were carried out in 4 substations in district heating system in Belgrade (Serbia). The main achievement of this research was that the fouling factors were determined experimentally, and the found values can be used further on in design of plate heat exchangers in district heating systems.
► Fouling factors for district heating heat exchangers are determined experimentally.
► The measurements were conducted over one year period.
► Fouling factor for domestic hot water is correlated with wall shear stress.
► Fouling factor for water in radiator heating system is found to be roughly constant.
Journal: Energy and Buildings - Volume 50, July 2012, Pages 204–211