کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
269680 | 504692 | 2016 | 14 صفحه PDF | دانلود رایگان |
• The non-piloted ignition temperature of spruce wood is highly variable.
• Ignition temperature is more variable for time-varying exposures than for constant.
• A numerical heat transfer model yields good predictions of ignition time.
• Predictions of ignition time are more accurate when the heating rate is greater.
Many studies have utilized a small-scale experimental apparatus such as the cone calorimeter to investigate the piloted ignition of wood exposed to constant levels of incident heat flux; however, there is a deficiency of similar studies related to the non-piloted ignition of wood exposed to time-varying heat fluxes which might represent more realistic fire exposures. In this study, a method was established for producing well-controlled, time-varying exposures using the conical radiant heater of a cone calorimeter. Experiments were conducted in which the incident flux, time to non-piloted ignition, and back-surface temperature of spruce wood were measured. Measured data were used in combination with a numerical heat transfer model to compute the time-dependent temperature distribution through each specimen, and thereby deduce the surface temperature at ignition. From the 30 specimens tested, the average surface temperature for non-piloted ignition of wood was determined to be 521±10 °C. From this surface temperature range, the heat transfer model was used to predict the range of time over which non-piloted ignition was likely to occur for a given time-varying exposure. This procedure was found to produce excellent predictions of ignition time for the time-varying exposures considered in this study. In addition, several existing ignition models were considered, and their suitability for predicting the non-piloted ignition of wood was assessed.
Journal: Fire Safety Journal - Volume 82, May 2016, Pages 131–144