کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
3373445 1219296 2007 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Isolation of Legionella species/serogroups from water cooling systems compared with potable water systems in Spanish healthcare facilities
موضوعات مرتبط
علوم زیستی و بیوفناوری ایمنی شناسی و میکروب شناسی میکروبیولوژی و بیوتکنولوژی کاربردی
پیش نمایش صفحه اول مقاله
Isolation of Legionella species/serogroups from water cooling systems compared with potable water systems in Spanish healthcare facilities
چکیده انگلیسی

SummarySurveillance of Legionella spp. in hospital water systems was performed in forty-four inpatient healthcare facilities in Spain during 2005–2006. A total of 2341 samples were collected: 470 from cooling systems (cooling towers) and 1871 from potable water systems. The latter included 211 from cold-water tanks and 260 from hot-water tanks, totalling 471 from central water reservoirs 136 from showers, 1172 from unfiltered taps and 92 from filtered taps, totalling 1400 from peripheral points. Temperature, chlorine levels and the presence of Legionella spp. were determined. In all, 373 (15.9%) samples yielded Legionella spp. Significantly higher isolation rates were obtained from cooling towers (23.8%) versus cold- and hot-water tanks (approximately 4.7%), due to the significantly higher number of samples positive for serogroup 1 (19.4 vs 0.9–3.5%). In potable water systems, no differences were found between central water tanks and showers, but significant differences in isolation rates between central water tanks and unfiltered taps were observed (4.7 vs 19.6%) due to differences in non-serogroup 1 L. pneumophila. Filters significantly decreased isolation rates of these serotypes (11 vs 0%). Some seasonal differences were noted, with higher isolation rates in summer for legionella serogroup 1 in cooling systems and for L. pneumophila serogroups 2–14 in potable water systems. In regression models, higher temperatures were associated with colonisation in cooling systems, while lower chlorine levels were associated with colonisation in potable water systems.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Journal of Hospital Infection - Volume 67, Issue 4, December 2007, Pages 360–366
نویسندگان
, , , , , , ,