چکیده انگلیسی


- Experimental research to measure the efficiency of high-pressure sprays in capturing aerosols if applied to a filtered containment venting system in case of severe accident.
- Cloud of monodispersed SiO2 particles with sizes 0.5 or 1.0 μm and initial concentration in the range 2-90 mg/m3.
- Carried out in a chamber 0.5 × 1.0 m and 1.5 m high, with transparent walls equipped with a high pressure water spray with single nozzle.
- Respect to low-pressure sprays, removal efficiency turned out significant: the half-life for 1 μm particles with a removal high-pressure spray system is orders of magnitude shorter than that with a low-pressure sprays system.

An experimental research was managed in the framework of the PASSAM European Project to measure the efficiency of high-pressure sprays in capturing aerosols when applied to a filtered containment venting system in case of severe accident.The campaign was carried out in a purposely built facility composed by a scrubbing chamber 0.5 × 1.0 m and 1.5 m high, with transparent walls to permit the complete view of the aerosol removal process, where the aerosol was injected to form a cloud of specific particle concentration. The chamber was equipped with a high pressure water spray system with a single nozzle placed on its top.The test matrix consisted in the combination of water pressure injections, in the range 50-130 bar, on a cloud of monodispersed SiO2 particles with sizes 0.5 or 1.0 μm and initial concentration ranging between 2 and 99 mg/m3. The spray was kept running for 2 min and the efficiency of the removal was evaluated, along the test time, using an optical particle sizer.With respect to low-pressure sprays, the removal efficiency turned out much more significant: the half-life for 1 μm particles with a removal high-pressure spray system is orders of magnitude shorter than that with a low-pressure spray system.The highest removal rate was detected with 1 μm particles at the highest water injection pressure, mainly because of the high concentration of droplets with high velocity, while lower removal was measured for 0.5 μm particles. No influence of the initial aerosol concentration was observed for both particle sizes.