کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
5001329 1460873 2016 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Investigating the influence of moisture on the 2FAL generation rate of transformers: A new model to estimate the DP of cellulosic insulation
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Investigating the influence of moisture on the 2FAL generation rate of transformers: A new model to estimate the DP of cellulosic insulation
چکیده انگلیسی
The analysis of the concentration of furanic compounds in oil has been accepted as one of the most reliable methods to obtain information about the condition of the transformer's cellulosic insulation. In this paper, the relation between the moisture content of the paper and the rate of generation of 2-furfuraldehidyde (2FAL) is studied. A statistical study is carried out to determine if transformers with higher moisture contents in oil tend to present higher contents of 2FAL, and, to this end, a database with more than 20,000 historical records of transformers is utilized. This study is completed with a set of accelerated ageing tests of transformer cellulosic insulation pieces, conditioned with different moisture contents. The impact of the moisture content of paper on the relation between the degree of polymerization (DP) and the 2FAL concentration is determined, and a correction factor has been proposed to include this variable in a model.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Electric Power Systems Research - Volume 140, November 2016, Pages 87-94