کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
6727935 1428921 2018 31 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
A new ventilated window with PCM heat exchanger-Performance analysis and design optimization
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
A new ventilated window with PCM heat exchanger-Performance analysis and design optimization
چکیده انگلیسی
Numerical model is built and verified by full-scale experiment to evaluate the PCM ventilation system. The nonlinear properties and hysteresis of PCM are set in the model. The conclusion is that the configuration optimization should be based on different climates. In the case study in Copenhagen, the heat exchanger with 10 mm plate thickness is optimized. It can cool down the ventilated air 6.5 °C on average in 3.9 h pre-cooling effective time with 3.19 MJ/day energy saving. The material cost saving is 16.87% compared to 20 mm plate thickness which has similar discharged heat amount. Nevertheless, the heat exchanger with 5 mm plate thickness has a faster thermal response and a higher cost saving ability, which is good for the climate when the period of outdoor air temperature suitable for night ventilation in a day is short.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 169, 15 June 2018, Pages 185-194