Revision of TRV requirements for the application of generator circuit-breakers
ترجمه فارسی عنوان
ویرایشهای مورد نیاز TRV برای استفاده از ژنراتور مدار قطع کننده
کلمات کلیدی
خطا در حال حاضر؛ ژنراتور مدار شکن؛ ولتاژ بازیافت گذرای
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
چکیده انگلیسی


• A review of TRV parameters for generator circuit-breaker applications has been done.
• For system-source faults TRV td can exceed the standardised values.
• For generator-source faults TRV E2/V can exceed the standardised values.
• In case of out-of-phase conditions.∘E2/V and RRRV increase with out-of-phase angle.∘td Seems to be somewhat constant with the out-of-phase angle.

The requirements imposed on generator circuit-breakers greatly differ from the requirements imposed on other transmission and distribution circuit-breakers. Due to the location of installation between the generator and the associated step-up transformer, a generator circuit-breaker must meet high technical requirements with respect to rated normal currents, short-circuit currents, fault currents due to out-of-phase conditions and transient recovery voltages. The question whether the transient recovery voltage requirements laid down in IEEE Std C37.013-1997 (R2008) and in IEC/IEEE 62271-37-013 are adequate for the application of generator circuit-breakers in modern power stations is considered in the present work.In order to quantify the transient recovery voltage requirements for the application of generator circuit-breakers a comprehensive survey of different fault conditions occurring in several power stations has been performed. The fault transients’ simulations have been performed by means of the Electromagnetic Transients Program (EMTP).

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Electric Power Systems Research - Volume 138, September 2016, Pages 66–71
نویسندگان
, , , ,