چکیده انگلیسی
This article deals with results of performed studies of transient phenomena in application of controlled switching technique by switching high voltage 123 kV, 100 MVAr shunt reactor. First, for switching a single-pole hydraulically operated SF6 circuit breaker has been selected and after that, one with electric motor-drive. In preparing of experimental part of studies the EMTP-ATP software has been used in computer simulations, further for analyses the cases of optimal controlled switching and switching within time deviation limits. For simulation of uncontrolled switching with current chopping and arc-reignition dynamic model of arc behavior has been implemented. The field tests with both circuit breakers have been repeated in similar network conditions for further statistical analyses. During some tests, the transient phenomena of uncontrolled switching have been observed. The achieved experimental results were compared with the computer simulations.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Electric Power Systems Research - Volume 162, September 2018, Pages 74-82