Synchronized measurement technology supported AC and HVDC online disturbance detection
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Synchronized measurement technology supported AC and HVDC online disturbance detection
چکیده انگلیسی
In electric power system, disturbance detection has become an important part of grid operation and refers to the detection of a voltage and current excursion caused by the wide variety of electromagnetic phenomena. This paper proposes a computationally efficient and robust algorithm for synchronized measurement technology (SMT) supported online disturbance detection, suitable for AC and HVDC grids. The proposed algorithm is based on the robust median absolute deviation sample dispersion measure to locate dataset outliers. The algorithm is capable of identifying the disturbance occurrence and clearance measurement sample based on the dynamic criteria, driven by present power system conditions. The effectiveness of the proposed algorithm is verified by real-time simulations using a cyber-physical simulation platform, as a co-simulation between the SMT supported electric power system model and underlying ICT infrastructure. The presented results demonstrate effectiveness of the proposed algorithm, making it suitable for an AC and HVDC online disturbance detection application or as a pre-step of backup protection schemes.