Evaluation of flammable volume in the case of a catastrophic leak of R-32 from a rooftop unit
چکیده انگلیسی
With the effort to use alternative refrigerants with lower global warming potential (GWP), the majority of these alternative refrigerants are classified as slightly flammable. In this paper we report on the numerical evaluation of a catastrophic leak scenario of R-32 refrigerant from a 3-ton roof top air conditioning unit (RTU) which serves a 12.2 × 9.14 × 2.4 m room. A full rupture of a 6.35 mm (¼ inch) pipe downstream of the evaporator coil is simulated. Two separate cases with refrigerant releases of 1.81 kg and 3.62 kg charge have been studied. The two charges are released in 10.2 and 20.4 s, respectively, just after the end of a unit cooling cycle. The flammable volume inside the room existed only for about 40 s with a maximum flammable volume inside the room of 1.12% of the total room volume for the 3.62 kg charge case.