Lithium bromide absorption machines: Pressure drop and mass transfer in solutions conical sheets
چکیده انگلیسی

Adiabatic vapour absorption in conical liquid sheets is studied with a view to use in air conditioning. The sheets consist in a lithium bromide aqueous solution sprayed at mass flow rates ranging from 0.0078 to 0.0116 kg/s (28–42 kg/h). The experimental results show that the deformation rate associated with conical sheet development has a significant effect on absorption, with 60% of the total reached by the time the liquid sheet disintegrates, 4 ms after injection. In the conical sheet configuration, about 150 g of vapour are absorbed per kJ of solution flow work. The vapour absorption rate per chamber absorption volume, in turn, is found to be over 1 g/s l in absorption chambers 75 mm long or less.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 50, Issue 7, July 2009, Pages 1802–1809