کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
245429 502000 2006 15 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Thermodynamic-behaviour model for air-cooled screw chillers with a variable set-point condensing temperature
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Thermodynamic-behaviour model for air-cooled screw chillers with a variable set-point condensing temperature
چکیده انگلیسی

This paper presents a thermodynamic model to evaluate the coefficient of performance (COP) of an air-cooled screw chiller under various operating conditions. The model accounts for the real process phenomena, including the capacity control of screw compressors and variations in the heat-transfer coefficients of an evaporator and a condenser at part load. It also contains an algorithm to determine how the condenser fans are staged in response to a set-point condensing temperature. The model parameters are identified, based on the performance data of chiller specifications. The chiller model is validated using a wide range of operating data of an air-cooled screw chiller. The difference between the measured and modelled COPs is within ±10% for 86% of the data points. The chiller’s COP can increase by up to 115% when the set-point condensing temperature is adjusted, based on any given outdoor temperature. Having identified the variation in the chiller’s COP, a suitable strategy is proposed for air-cooled screw chillers to operate at maximum efficiency as much as possible when they have to satisfy a building’s cooling-load.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Energy - Volume 83, Issue 3, March 2006, Pages 265–279
نویسندگان
, ,