کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
10286001 504067 2014 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Raw-water source heat pump for a vertical water treatment building
ترجمه فارسی عنوان
پمپ حرارتی منبع خام برای یک ساختمان تصفیه آب عمودی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
چکیده انگلیسی
A raw-water source heat pump for a thermal storage tank in a vertical water treatment building was dynamically simulated by TRNSYS. Two different configurations of a heat pump system with either one or two heat pumps were investigated by considering different heating zones in the building. The average COPs of the single heat pump system were 4.79 and 3.76 for cooling and heating, respectively. When the size of the thermal storage tank was changed from 5 m3 to 15 m3, the highest COP was found at 10 m3. The electric power consumption of the heat pump was significantly affected by weather conditions. The average COPs of the two-heat-pump system were 4.92 and 3.68 for cooling and heating, respectively. Except April and October the monthly average COP of the two-heat-pump system was higher than that of the single-heat-pump system.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 68, Part A, January 2014, Pages 321-328
نویسندگان
, , ,