کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
10286542 504200 2005 6 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Fault-tolerant control and data recovery in HVAC monitoring system
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Fault-tolerant control and data recovery in HVAC monitoring system
چکیده انگلیسی
It is necessary that a reliable and optimal control system has the ability of fault tolerance, which recovers the faulty and/or missed data in time. Principal component analysis (PCA) is presented to model HVAC monitored systems by using the measured data under normal operation condition (NOC). PCA splits the measurement space into two subspaces, one principal component subspace (PCS) and the other residual subspace (RS). When the faulty or missed data is observed, it will be projected into PCS and RS. It is then recovered by sliding the faulty or missed data to PCS via iteration. Examples of HVAC monitoring system have demonstrated that the approach has good performance to recover faulty or missed data and thus can be embedded into the system to achieve fault-tolerant control.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 37, Issue 2, February 2005, Pages 175-180