کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
1510613 1511165 2015 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Exergetic Analysis of a GAX Refrigeration System Design to Operate with LP Gas and Solar Energy
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Exergetic Analysis of a GAX Refrigeration System Design to Operate with LP Gas and Solar Energy
چکیده انگلیسی

An exergetic analysis was made to a GAX refigeration cycle. This GAX refigeration system was designed to produce 10 kW cooling power using two thermal sources, LP gas and solar energy, the system used to be air cooled avoiding the cooling tower. The methodology of exergetic cost was used to identify which part of the system generates the most irrerversibilites. The results indicates the absorber, the generator and the rectifier are the most irreversible components of the system. The sum of these three components irreversibilities represent the 58% of the total irreversibility. The exergetic cost was calculated for all of the flows of the GAX refrigeration cycle, the unit exergetic cost of the heat flow at the evaporator is 6.8. The highest exergetic cost was found in the solution coming out of the rectifier to the generator heat exchanger.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Procedia - Volume 70, May 2015, Pages 644-651