Performance Evaluation of 35 kW LiBr–H2O Solar Absorption Cooling System in Thailand
چکیده انگلیسی

The aim of this work was to evaluate the performance of a 35 kW LiBr-H2O absorption machine driven by 72 m2 heat pipe evacuated tube collector with a gas backup system, by analyzing the COP based on the manufacturer's specifications. The results from this study showed that actual average COP of the system was 0.33 while the maximum and minimum values were 0.50 and 0.17 respectively. These results were obtained based on the average collector efficiency and the solar fraction of 0.55 and at an ambient temperature of 32 °C.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Procedia - Volume 34, 2013, Pages 198-210