Analysis of the Performance of a GAX Hybrid (Solar - LPG) Absorption Refrigeration System Operating with Temperatures from Solar Heating Sources
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Analysis of the Performance of a GAX Hybrid (Solar - LPG) Absorption Refrigeration System Operating with Temperatures from Solar Heating Sources
چکیده انگلیسی

This paper presents the analysis of the experimental tests performed with an absorption refrigeration advanced Solar-GAX system, designed for 10.5 kW (3 Ton) of cooling using ammonia-water mixture. The system designed for operation at heat source temperatures of around 200°C, consists of an absorber and generator of a falling film type and air cooled finned tube condenser and absorber, being an option for areas with water scarcity. Heat source temperatures of 160°C were established to simulate the conditions of using solar thermal concentrating technology to supply heat the system, this means the system operating at partial load. Cooling capacities from 3 to 7 kW were obtained, with an average coefficient of performance (COP) of 0.37. Thermal stability was rapidly reached, after only 15 minutes of operation.