کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
1514105 | 1511219 | 2012 | 10 صفحه PDF | دانلود رایگان |

In this study is presented a thermodynamic analysis of a cascade refrigeration system using as refrigerant carbon dioxide in low-temperature circuit and ammonia in high-temperature circuit. The operating parameters considered in this paper include condensing, evaporating, superheating and subcooling temperatures in the ammonia (R717) hightemperature circuit and in the carbon dioxide (R744) low-temperature circuit. Diagrams of COP versus operating parameters have been obtained. In addition, values for R744-R717 cascade refrigeration system are compared with the values obtained for a partial injection two-stage refrigeration system using the synthetic refrigerant R404A, a nearly azeotropic blend, specially used for commercial refrigeration. Results show that a carbon dioxide-ammonia cascade refrigeration system is an interesting alternative to R404A two-stage refrigeration system for low evaporating temperatures (–30 °C ÷ –50 °C) in commercial refrigeration for energy, security and environmental reasons.
Journal: Energy Procedia - Volume 14, 2012, Pages 56-65