کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
1514194 1511219 2012 6 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
The applied effect analysis of heat exchanger installed in a typical communication base station in Beijing of China
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
The applied effect analysis of heat exchanger installed in a typical communication base station in Beijing of China
چکیده انگلیسی

The high electric power consumption of air conditioning in communication base station needs to be solved urgently. This paper presents a new technology to discharge excess heat from a communication plant by utilizing the heat exchanger when the outdoor temperature is low enough. Then it compares the applied effects between two types of heat exchanger in a typical base station located in Beijing of China. It is found that this technology is feasible in Beijing of China. The plate heat exchanger can cool the station instead of air conditioning for about 5014 hours each year, and the corresponding electronic power saving rate reaches up to 29%. The plate heat exchanger applied effects are superior to the heat pipe heat exchanger.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Procedia - Volume 14, 2012, Pages 620-625