کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
243045 501916 2013 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Continuous heating of an air-source heat pump during defrosting and improvement of energy efficiency
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Continuous heating of an air-source heat pump during defrosting and improvement of energy efficiency
چکیده انگلیسی


• The newly designed dual hot gas spray defrosting method was examined.
• Uninterrupted heating of an air source heat pump during defrosting.
• We compared newly designed dual hot gas and traditional reverse cycle defrost.
• Total energy efficiency was increased by 8% compared to traditional method.

During winter operation, an air-source heat pump extracts heat from the cold outside air and releases the heat into the living space. At certain outside air conditions, when it operates in heating mode, frost can form on the air-cooled heat exchanger, decreasing the heating performance. Conventionally, reverse-cycle defrosting (RCD) has been the common method of frost removal. But this method requires the interruption of heating during defrosting, as well as a period of time to reheat the cooled pipes of the indoor units after defrosting. In this study, a new technology called continuous heating was developed, which utilize only a hot gas bypass valve to remove the frost from the outdoor heat exchanger and thus enabling the supply of hot air to indoors without any interruption. For this, a new high temperature and low pressure gas bypass method was designed, which is differentiated from the common high pressure hot gas bypass methods by its use of low pressure. Various refrigerant mass flow distributions were examined, and the most effective defrosting mass flow was 50% in this case. Heating capacity was increased by 17% because of continuous heating, and the cumulated energy efficiency was increased by 8% compared to the traditional reverse cycle defrosting over 4 h including two defrost operations. Also, cumulated energy efficiency was increased by 27% compared to electronic heaters that supply the same heating capacity during defrosting. By this new technology, it has been proved that continuous heating and energy savings could be achieved without adopting expensive technologies.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Energy - Volume 110, October 2013, Pages 9–16
نویسندگان
, , , ,