کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
245139 501972 2008 10 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Development of a method for calculating steady-state equipment sensible heat ratio of direct expansion air conditioning units
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Development of a method for calculating steady-state equipment sensible heat ratio of direct expansion air conditioning units
چکیده انگلیسی

A complete set of calculation method for steady-state equipment sensible heat ratio (SHR) for a direct expansion (DX) cooling coil has been developed and reported. The method was based on the fundamentals of energy conservation and heat and mass transfer taking place in the DX cooling coil, and was experimentally validated using an experimental DX A/C rig. With the method developed, the effect of refrigerant evaporating temperature at fixed inlet air conditions on equipment SHR has been theoretically analyzed. The validated method can be useful in further studying the inherent operating characteristics of a DX air conditioning (A/C) unit and in developing suitable control strategies for achieving higher energy efficiency and better indoor thermal environment.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Energy - Volume 85, Issue 12, December 2008, Pages 1198–1207
نویسندگان
, , ,